介绍summary
Pumped storage power station as a special power, has flexible operation and fast response characteristics, with peak clipping, frequency modulation, phase modulation, and black start emergency backup in various functions in power system. Compared with the conventional power, pumped storage power plant can adapt to the rapid changes of the load, the important role in improving power system safe and stable operation, power supply quality and reliability of power grid, with "Kyushin Pills".
The M G C 6000 series speed regulator is a cross full redundancy system, and the two computers communicate with each other through the T C P / I P network. Two sets of programmable microcomputer regulator system with independent power supply, stable operation of the governor: "stop waiting" and "turbine (no-load)" and "power generation" (load), "phase", "drag motivation condition, pump phase modulation (" reversal ", no load) pump condition (reverse load). Among them, the "turbine operating mode" (no-load) and "water phase modulation" (reversing no-load) is not optional stability conditions, that is, into other conditions of the necessary process. The difference between the running condition and the conventional unit is the unique working condition of the reversible unit the water pump steering (reverse) part.
The utility model is suitable for a full range of pumped storage reversible units
-
Dual controller
-
Single (double) Regulation
-
Medium, large and large speed governor
-
lDual electro hydraulic redundancy converter
-
lThe utility model has the advantages of simple structure, convenient disassembly and maintenance
-
lReliable operation and little noise
-
Motor + proportional valve or dual proportional valve control system
-
Electromechanical cabinet or electromechanical cabinet
技术参数 Technical Parameter
技术参数 Specifications
|
技术指标 Technical Data
|
Cabinet characteristics
|
Dimension of cabinet of electromechanical joint cabinet
|
800mm*800mm*1860mm (length * width * height) can be customized
|
Cabinet weight
|
300kg
|
AC voltage standard for work
|
AC220V±15%
|
Operating DC voltage standard
|
DC110V±10%,DC220V±15%
|
Load capacity
|
3000W(VA)
|
Withstand voltage test
|
1.5kV,1min
|
Protection level
|
IP65
|
Operating temperature range
|
-40~65℃
|
Insulation impedance
|
>10MΩ
|
leakage current
|
<1mA
|
Control signal output
|
servo motor
|
Servo motor drive outlet
|
Proportional valve
|
Analog channel current 4~20mA
|
Input characteristic
|
Switch input
|
DC24V,LED Indicator light, fully isolated
|
Analog input
|
Voltage 0 ~ 10V, current 4 ~ 20mA, LED indicator light, completely isolated
|
output characteristic
|
On-off output
|
DC24V,LED Indicator light, fully isolated
|
Analog output
|
Voltage 0 ~ 10V, current 4 ~ 20mA, LED indicator light, completely isolated
|
Frequency measurement specification
|
Measurement mode
|
Controller body frequency measurement
|
Grid frequency
|
Alternating current (30 ~ 150V), rated frequency from 90 to 110%
|
Unit frequency
|
Alternating current (0.3 ~ 150V), 7.8 to 110 Hz
|
Frequency measurement of gear disc
|
Contactless proximity switch (DC24V power supply) 1~110 Hz
|
Frequency measuring resolution
|
0.001Hz
|
Frequency measuring channel
|
Unit residual pressure frequency, system frequency, unit gear speed measurement
|
|
性能参数 performance parameter
性能参数 Specifications
|
技术指标 Technical Data
|
Stability performance
|
Relative value of unit speed swing
|
<±0.15%
|
Gateopening stable fluctuation value
|
<0.1%
|
Maximum nonlinearity of static characteristic curve
|
<0.3%
|
Speed dead zone
|
<0.02%
|
Dynamic characteristics
|
Power generation automatic turn on time
|
30~120s 可设定
|
Back to back automatic start time
|
100~300s 可设定
|
Parameter setting of speed regulation system
|
The adjustment range of the permanent slip coefficient is
|
0~10%
|
Slip adjustment range is
|
0~10%
|
Adjust the frequency range of the manual frequency on line
|
0~±1.5%
|
Speed adjustment range is
|
90~110%
|
The power adjustment range is
|
0~105%
|
Zero load and full load adjustment time
|
20~300s
|
Mode of operation, switching, relay changes
|
<0.3%
|
Dual power switching relay changes
|
<0.1%
|
Dual controller switching relay changes
|
<0.1%
|
Proportional gain Kp range
|
0~20
|
Integral gain Ki range
|
0.01~10(1l/s)
|
Differential gain Kd range
|
0.01~10s
|
The reliability of power generation direction conversion is not less than
|
100.00%
|
The reliability is not less than that of pumping direction
|
100.00%
|
The speed regulation system can be utilized not less than
|
99.99%
|
The first trouble free interval is not less than
|
30000
|
|