The utility model is suitable for measuring, locating and alarming a generator of various capacity, a synchronous exciter, an exciting circuit (rotor), and a ground point.
Ø Power input:The working power supply can be AC and DC common, and has strong adaptability to the power supply;
Ø Real-time calculation:The high performance CPU processor guarantees real-time computation of all relays for each sampling point.
Ø Precise measurement and location:An advanced injection voltage rotor grounding resistance measurement method is adopted to ensure the accuracy of measurement and positioning;
Ø LCD:Real time display device, sampling, setting, reporting, waveform and so on;
Ø Message logging:Record event message, including action information and action waveform;
Ø Parameter setting:Can limit parameters of grounding in traditional settings, Cancel buttons, the touch screen input operation more intuitive and convenient;
Ø External communication:Provide RS485 communication connection, remote communication device current state and action information;
Ø Alarm output:A separate device for power loss alarm is provided, and the two section insulation is limited to alarm, and each alarm signal is provided with two way nodes;
Ø Indicator light:May indicate the current power status, device operation state, alarm status and so on;
Ø Self-test function:The device has self inspection and troubleshooting, self recovery function;
Ø Print function:Provides a serial port for connecting printers;
Ø Installation method:The utility model has the advantages of small size and beautiful appearance, and the opening hole is installed;
Ø Other:The device shall be used in conjunction with the B-BH-ZF accessory. When the device cooperates with other rotor ground protection, the rotor main shaft wiring shall be properly switched.
Ø Working storage temperature:-25~+65℃;
Ø Ambient humidity:≤ 95%,无凝露。
Ø Power input:AC/DC220V(50/60Hz);
Ø Power waste:Not greater than30W;
Ø Setting range of insulation:1.0KΩ~50.0KΩ;
Ø Insulation measurement error:±0.5KΩ(resistance≤5 KΩ),not exceeding ±10% (resistance>5 KΩ);
Ø Position measurement error:No more than 1 pairs of magnetic poles;
Ø Display range:Voltage 0.1-600V,resistance 0-500KΩ;
Ø Alarm contact: 5A30VDC,5A250VAC;
Ø Other:For special requirements, please specify when ordering.